Overview
BA Analog Current Sensor/current transducer apply the principle of electromagnetic induction to measure the AC current in the power grid in real time, and use constant current and linear compensation technology to isolate and transform it into a standard DC signal output. Most use in industrial automation for PLC.
Parameter
|
BA05-AI/I(V) |
BA10-AI/I(V) |
BA20-AI/I(V) |
BA50-AI/I(V) |
BA50L-AI/I(V) |
||
|
Auxiliary power |
DC 12V |
DC 12V DC 24V |
DC 12V DC 24V |
DC 12V DC 24V |
DC 12V DC 24V |
DC 12V DC 24V |
| DC 24V | ||||||
|
Consumption |
≤1W |
≤1W |
≤1W |
≤1W |
≤1W |
|
|
Through-hole size |
φ5mm |
φ10mm |
φ20mm |
φ50mm |
φ50mm |
|
|
Input |
Current |
AC 0~(0.5~10)A |
AC 0~(8~50)A |
AC 0~(40~200)A |
AC 0~(60~600)A |
AC 0~(0.1~1)A (limitation of leakage currents) |
|
Output |
Nominal value |
DC4-20mA,or 0-20mA,0-5V,0-10V etc |
||||
|
Load resistance |
Current output≤500Ω,Voltage output≥1kΩ |
|||||
|
Accuracy Class |
0.5% |
|||||
|
Response time |
≤350ms |
|||||
|
Temperature |
Operation:-10 to +55℃ Storage:-25 to +70℃ |
|||||
|
Temperature coefficient |
≤200ppm/℃ |
|||||
|
Installation |
(Rail)DIN35,fix on cubicle with screws |
|||||
|
Standards |
GB/T 13850 |
|||||
![]() |
BA50-AI/I ●Input: 0-1A Leakage Current ●Output: DC 4-20mA ●Measurement of Leakage Current ●Overload: 1.2 times of Rated Value |
|
BA20-AI/V ●Application: Industrial automation ●Input: AC current measurement up to 200A ●Overload: 1.2 times of the rated value ●Output: DC 0-5V |
|
Appearance

●Higher accuracy ●Higher Level of Isolation ●Higher Safety Level ●Lower Consumption
Dimensions

Installation

Choose a suitable place to install the standard DIN35mm rail, and install the BA sensor on the rail;

On the bottom panel of the cabinet, choose a suitable place to open two threaded holes corresponding to the position of the fixed hole of the installed sensor; After placing the sensor, install the positioning screw
Wiring

1 —— + Positive power supply (not reversed)
2 —— - Power EARTH
3 —— G(Current output negative, which can be shared with the power supply)
4 —— IDC(Current output positive),VDC(Voltage output positive)
Application

Quotation

Hot Tags: 4-20ma current transducer, China 4-20ma current transducer manufacturers, suppliers, factory, 4 20MA Current Transducer, AC Voltage Transducer, 0 5V current transducer, Multi Channel Transmitter, Intelligent Current Transducer, 4 20ma Voltage Transducer