Overview
Our Intelligent Current Transducers are sensors specially used to convert the raw voltage and current in the power system into useful electrical signals, and then forward these electrical signals to the controller or PLC, process and record them, these electrical signals can be used in the measurement system use and transmission. They are small in size and easy to install and remove, which can help you effectively save assembly time and space. And they come with higher monitoring accuracy than conventional sensors, and can measure current efficiently even in less wiring or low-voltage environments.
Features
Our Intelligent Current Transducers keep track of the condition of electrical wiring and equipment, preventing fires and other accidents caused by leaks and effectively safeguarding the safety of users and their equipment. They provide you with clear and easy-to-use signals, offering efficient performance for servo drives or other high-precision applications. The pure copper coils inside provide high conversion power while have long service time. In addition they are supplied with a dotted rubber encapsulated potentiometer for increased vibration resistance and effective protection against current disturbances.

Parameter
|
Technical parameter |
Index | ||
|
Accuracy class |
Class 0.5 | ||
|
Input |
Nominal value |
BA20(Ⅱ)-AI |
Current AC 0.5A, 50A, 200A, etc. AC 0~(0.5~200)A |
|
BA50(Ⅱ)-AI |
Current AC 60A, 300A, 600A, etc. AC 0~(60~600)A |
||
|
BA50L(Ⅱ)-AI |
Current AC 0.1A, 1A, etc. AC 0~(0.1~1)A |
||
| Overload |
Continuous 1.2 times, instantaneous current 10 times/1S |
||
|
Absorbed power |
≤1VA |
||
|
Frequency response |
25Hz~800Hz, especially suitable for industrial frequency |
||
|
Output |
Nominal value |
DC4~20mA, or 0~20mA, 0~5V, 0~10V① etc. |
|
|
Load Resistance |
When DC12V power supply, current output Class 0.5is ≤250Ω When DC24V power supply, current output is ≤500Ω, When voltage output is ≥1KΩ |
||
|
Communication |
RS485 interface/Modbus-RTU② |
||
|
Response time |
≤400ms | ||
|
Power supply |
Voltage |
12V or 24V |
|
|
Power consumption |
≤1W |
||
|
Insulation resistance |
>100MΩ | ||
|
Compressive strength |
Between input/output and power supply 2.0KV/1min,50Hz |
||
|
Temperature Coefficient |
-10℃~+55℃, ≤400ppm/℃ |
||
|
Environment |
Temperature |
Work: -10℃~+55℃ Storage: -25℃~+70℃ |
|
|
Humidity |
≤93%RH, no condensation, no corrosive gas place |
||
|
Altitude |
≤2000m |
||
|
Installation method |
TS35 rail, or use screws to fix the cabinet | ||
Note: ①0~10V output is only suitable for DC24V power supply;
②The communication function is optional.
![]() |
BA10-AI/I ●Application: Industrial automation ●Input: AC current measurement up to 50A ●Overload: 1.2 times of the rated value ●Output: DC 4-20mA |
|
BA20-AI/V ●Application: Industrial automation ●Input: AC current measurement up to 200A ●Overload: 1.2 times of the rated value ●Output: DC 0-5V |
![]() |
Appearance

Dimensions


Integrated Installation

Integrated installation, a rotating structure can be used in the perforated part.

There are Φ20, Φ50 of hole sizes for your selection.

The main body could be connected to the display screen in order to display current and set parameters when integrated installation (use existing display screen as far as possible)
Split-type Installation

The current transformer is connected to the main body through a network cable when using the split-type connection.

TS3 din-rail mounting, or fix it on the cabinet with screws
Quotation