Information
Characteristic
1)Communication: RS485/Modbus-Rtu
2)Multi-circuit: A+B independet 2 circuit DC24V output
3)Rated U and I: U:DC48V/240V/336V I:5V
Function
|
1. A+B independent two DC lines of voltage, current, power, electric energy,
2. Channel temperature and humidity monitoring
3. 8 Switching status inputs
4. 4 switching status outputs
5. 3 RS485 communications |
Installation DIN 35mm
Dimension(L*W*H): 180*90*45 |
|
Appearance



Wiring
Parameter
Distribution System |
DC |
|
Bus voltage |
Rated voltage |
48VDC,240VDC,336VDC
|
Measuring range |
±20% |
|
Overload |
Instantaneous voltage 2 times per second
|
|
Current incoming circuit |
Rated |
5V(Hall sensor, ±12V powered by AMC100-ZD)
|
Overload |
Duration is 1.2 times, instantaneous 10 times/second
|
|
Environment
|
Altitude
|
≤2500m
|
Temperature |
Operation:-15℃~55℃ Storage:-25℃~70℃
|
|
Humidity |
Relative humidity≤93%
|
|
Installation
|
Method DIN35mm rail or bottom plate installation
|
|
Auxiliary power supply |
AMC100-ZD:Signal power(≤15W) AMC100-ZD-P24:DC 12-24V independent power supply AMC100-ZD-P220: 1、When the constant voltage is DC240V、DC336V,powered by AC220V、 DC240V、DC336V independent supply 2、When the constant voltage is DC48V,powered by DC48V independent supply
|
|
Insulation resistance |
The insulation resistance between all terminals and the conductive parts on the shell must be at least 100MΩ
|
|
Switch output |
4 channels 3A 250VAC/3A 30VDC |
|
Switch input |
8 dry nodes |
|
Communication |
1 channel isolatedRS485/Modbus-RTU to the background system 1RS485/Modbus-RTU to touch screen 1RS485/Modbus-RTU connection to the downstream module 1-channel Ethernet communication function is optional
|
|
Installation |
DIN35mm rail or bottom plate installation |
Quotation
Shape |
Type |
Function |
FOB Shang Hai (USD) |
![]() |
AMC100-ZA |
Monitoring the full power parameters of the A+B dual three-phase AC incoming circuit, 8 switching status inputs, 4 switching status outputs, 2 leakage monitoring, 1 temperature and humidity detection, 3 RS485 communications |
148 |
![]() |
AMC-FA30 |
Monitor the full power parameters of a total of 30 branches of A+B dual AC outlets, and 1 RS485 communication |
133 |
![]() |
AMC-FA48 |
Monitor the full power parameters of a total of 48 branches of A+B dual AC outlets, and 1 RS485 communication |
177 |
![]() |
AMC-FAK30 |
Monitor the full power parameters and switch status of a total of 30 branches of A+B dual AC outlets, and 1 RS485 communication |
177 |
![]() |
AMC-FAK48 |
Monitor the full power parameters and switch status of a total of 48 branches of A+B dual AC outlets, and 1 RS485 communication |
237 |
![]() |
AMC100-ZD |
Monitors the voltage, current, power, and electric energy of 2 independent incoming lines A+B,8 switching input, 4 switching output , 1 temperature and humidity detection, and 3 RS485 communications |
148 |
![]() |
AMC100-FD30 |
Monitor the full power parameters of A+B dual DC outgoing lines in A total of 30 branches, and 1 RS485 communication |
133 |
![]() |
AMC-FD48 |
Monitor the full power parameters of A+B dual DC outgoing lines in A total of 48 branches, and 1 RS485 communication |
177 |
![]() |
AMC100-FDK30 |
Monitor the full power parameters and switching status(active) of A+B dual DC outlet 30 branches,and 1 RS485 communication |
177 |
![]() |
AMC100-FDK48 |
Monitor the full power parameters and switching status(active) of A+B dual DC outlet 48 branches, and 1 RS485 communication |
237 |
Hot Tags: Data Center Main Incoming Line Power Meter, China Data Center Main Incoming Line Power Meter manufacturers, suppliers, factory, Wireless 3 Phase Energy Meter, Single Phase Prepaid Energy Meter, Wireless Three Phase AC Energy Meter, DC Power Meter, wifi energy meter, Three Phase Prepaid Energy Meter