Information
Characteristic
1)Communication: RS485/Modbus-Rtu
2)Multi-circuit: 30 circuit
3)Rated U and I: U:AC 220V/380V I:5A
Function
|
|
1. A+B independent two DC lines of voltage, current, power, electric energy
2. 30 switch status detection
3. 1 RS485 communications |
|
Installation DIN 35mm
Dimension(L*W*H): 144*90*45 |
|
Appearance



Wiring


Parameter
|
Distribution System |
DC |
|
|
Bus voltage |
Rated voltage |
48VDC,240VDC,336VDC
|
|
Measuring range |
±20% |
|
|
Overload |
Instantaneous voltage 2 times per second
|
|
|
Current incoming circuit |
Rated |
5V (Hall sensor, need external power supply ±12V or ±15V)
|
|
Overload |
Duration is 1.2 times, instantaneous 10 times/second
|
|
|
Environment
|
Altitude
|
≤2500m
|
|
Temperature |
Operation:-15℃~55℃ Storage:-25℃~70℃
|
|
|
Humidity |
Relative humidity≤93%
|
|
|
Installation
|
Method DIN35mm rail or bottom plate installation
|
|
|
Auxiliary power supply |
Powered by AMC100-ZD; DC 12-24V power supply when used alone
|
|
|
Insulation resistance |
The insulation resistance between all terminals and the conductive parts on the shell must be at least 100MΩ
|
|
|
Communication |
RS485/Modbus-RTU
|
|
|
Protection level
|
IP20 |
|
Quotation
|
Shape |
Type |
Function |
FOB Shang Hai (USD) |
![]() |
AMC100-ZA (2 Incoming Line) |
1. AC Data Center System 2. Monitoring the full power parameters of the A+B dual three-phase AC Incoming Circuit 3. 8 Switching status inputs 4. 4 Switching status outputs 5. 2 Leakage monitoring 6. 1 Temperature and humidity detection, 7. 3 RS485 communications |
148 |
![]() |
AMC-FA30 (30 Outgoing Line) |
1. AC Data Center System 2. Monitor the full power parameters of a total of 30 branches of A+B dual AC outgoing circuits 3. 1 RS485 communication |
133 |
![]() |
AMC-FA48 (48 Outgoing Line) |
1. AC Data Center System 2. Monitor the full power parameters of a total of 48 branches of A+B dual AC outlets 1 3. RS485 communication |
177 |
![]() |
AMC-FAK30 (30 Outgoing Line) |
1. AC Data Center System 2. Monitor the full power parameters of a total of 30 branches of A+B dual AC outgoing line 3. Switch the status of a total of 30 branches of A+B dual AC outgoing line 4. 1 RS485 communication |
177 |
![]() |
AMC-FAK48 (48 Outgoing Line) |
1. AC Data Center System 2. Monitor the full power parameters of a total of 48 branches of A+B dual AC outgoing line 3. Switch the status of a total of 48 branches of A+B dual AC outgoing line 4. 1 RS485 communication |
237 |
![]() |
AMC100-ZD (2 Incoming Line) |
1. DC Data Center System 2. Monitors the voltage, current, power, and electric energy of 2 independent incoming lines A+B 3. 8 Switching input 4. 4 Switching output 5. 1 Temperature and humidity detection 6. 3 RS485 communications |
148 |
![]() |
AMC100-FD30 (30 Outgoing Line) |
1. DC Data Center System 2. Monitor the full power parameters of A+B dual DC outgoing lines in A total of 30 branches 3. 1 RS485 communication |
133 |
![]() |
AMC-FD48 (48 Outgoing Line) |
1. DC Data Center System 2. Monitor the full power parameters of A+B dual DC outgoing lines in A total of 48 branches 3. 1 RS485 communication |
177 |
![]() |
AMC100-FDK30 (30 Outgoing Line) |
1. DC Data Center System 2. Monitor the full power parameters and switching status(active) of A+B dual DC outlet 30 branches 3. Switching status(active) of A+B dual DC outlet 30 branches 4. 1 RS485 communication |
177 |
![]() |
AMC100-FDK48 (48 Outgoing Line) |
1. DC Data Center System 2. Monitor the full power parameters and switching status(active) of A+B dual DC outlet 48 branches 3. Switching status(active) of A+B dual DC outlet 48 branches 4. 1 RS485 communication |
237 |
Hot Tags: Data Center 30 Branch Circuits DC Energy Meter, China Data Center 30 Branch Circuits DC Energy Meter manufacturers, suppliers, factory, DC Panel Power Meter, DC multi circuits energy meter, Din Rail DC Power Meter, Branch Circuit DC Meter for Data Center, Branch Circuit DC Meter, Energy Meter





















